The Genie 608964.0004.S is a Heat Detector designed for commercial and industrial access control applications. Fixed-temperature heat detector, 194 deg F activation, high-temp variant. Operating voltage: 6-125 VAC, 6-28 VDC. Compatible with Single-gang electrical box, 3.5 in octagonal box, 4 in octagonal box, and more.
| Feature | Specification |
|---|---|
| Model | Genie 608964.0004.S |
| Item Type | Heat Detector |
| Voltage | 6-125 VAC, 6-28 VDC |
| Contact Configuration | Normally open (NO) contact; non-resettable single-use |
| Dimensions | 4.57 in dia x 1.69 in H |
| Mounting | Single-gang box, 3.5 in or 4 in octagonal box, 4 in square box with plaster ring |
A: The 5604 activates at 194 deg F (90 deg C), which is significantly higher than the 135 deg F of the standard 5603. It is intended for high-temperature environments.
A: The maximum ambient installation temperature for the 5604 is 150 deg F (66 deg C), compared to 100 deg F for the 5603, making it suitable for attics, industrial spaces, or other hot areas.
A: No. The 5603 and 5604 have different activation temperatures and are not interchangeable. Using the wrong detector could result in delayed or failed activation in a fire event.
A: No, it is a non-resettable single-use device. After activation the entire unit must be replaced.
A: It supports 6-125 VAC at 3A and 6-28 VDC at 1A through a normally open contact.