The Genie 608964.0001.S is a Combination Smoke and Heat Detector designed for commercial and industrial access control applications. 4-Wire Photoelectric Smoke and Fixed-Temperature Heat Combo Detector. Operating voltage: 12VDC, 24VDC, 8.5-35VDC non-polarized. Compatible with System Sensor i3 Series compatible fire alarm panels, 4-wire fire alarm control panels, 12VDC systems, and more.
A: The 4WT-B combines a photoelectric smoke sensor and a fixed-temperature thermal heat sensor. The T indicates the built-in thermal element, and the 4W indicates a 4-wire (separate power and signal) wiring configuration.
A: The heat element triggers at a fixed temperature of 135 deg F (57.2 deg C). A freeze trouble alert is generated if temperature falls to 41 deg F (5 deg C).
A: It operates on 12VDC or 24VDC non-polarized within a range of 8.5 to 35VDC. Alarm current is 20 mA at 12V and 23 mA at 24V, with standby at approximately 50 uA.
A: The relay contact is Form C rated at 0.5A at 30V AC/DC, allowing integration with auxiliary devices or panel supervised circuits.
A: It mounts on 3.5-inch or 4-inch octagonal boxes, single-gang boxes, 4-inch square boxes with a plaster ring, or directly to the ceiling.