The Genie 608964.0005.S is a Combination Smoke and Heat Detector designed for commercial and industrial access control applications. 2-Wire Photoelectric Smoke and Fixed-Temperature Heat Combo Detector. Operating voltage: 12VDC, 24VDC, 8.5-35VDC non-polarized. Compatible with System Sensor i3 Series compatible fire alarm panels, 2-wire fire alarm control panels, 12VDC systems, and more.
A: The T suffix indicates the detector includes a thermal heat sensing element in addition to the photoelectric smoke sensor. It provides a fixed-temperature heat alarm at 135 deg F (57.2 deg C).
A: The heat element triggers a fixed-temperature alarm at 135 deg F (57.2 deg C). It also provides a freeze trouble alert if the temperature drops to 41 deg F (5 deg C) or below.
A: The alarm current is panel-limited with a maximum of 130 mA. Standby current is approximately 50 uA.
A: The operating temperature range is 32 to 100 deg F. It is intended for conditioned interior spaces and is not rated for extreme temperature environments.
A: It supports mounting on 3.5-inch or 4-inch octagonal boxes, single-gang boxes, 4-inch square boxes with a plaster ring, or direct ceiling mounting.